mirror of
https://github.com/unpoller/unpoller.git
synced 2026-03-31 06:33:57 -04:00
feat: UPS battery metrics, example Prometheus/Loki alerts (unpoller#930) (#941)
This commit is contained in:
210
alerts/README.md
Normal file
210
alerts/README.md
Normal file
@@ -0,0 +1,210 @@
|
||||
# UniFi Infrastructure Alerts
|
||||
|
||||
Example Prometheus and Loki alerting rules for monitoring UniFi infrastructure with unPoller.
|
||||
|
||||
## Overview
|
||||
|
||||
- **Prometheus** – Metrics from devices, clients, UPS/PDU, controller, sites, WAN, DHCP, rogue APs, and more
|
||||
- **Loki** – Logs for events, alarms, IDS, anomalies, and system logs
|
||||
|
||||
These examples assume the default Prometheus namespace `unpoller`. Adjust metric names if you use a custom `prometheus.namespace`.
|
||||
|
||||
---
|
||||
|
||||
## Prometheus Alerts
|
||||
|
||||
Place `prometheus/unifi-alerts.yaml` in your Prometheus `rule_files` or Grafana Alerting.
|
||||
|
||||
### UPS (unifi-ups)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiUPSLowBattery** | Battery level < 20% for 5m | warning | UPS needs attention; plan for charging or replacement |
|
||||
| **UnifiUPSCriticalBattery** | Battery level < 10% for 2m | critical | UPS near depletion; prepare for shutdown |
|
||||
| **UnifiUPSOnBattery** | Running on battery for 1m | warning | Power outage or AC loss; UPS sustaining load |
|
||||
| **UnifiUPSLowRuntime** | Runtime < 5 min (and known) for 5m | warning | Little runtime left; prioritize critical loads |
|
||||
| **UnifiUPSHighLoad** | Load > 80% of capacity for 10m | warning | UPS near capacity; consider load shedding |
|
||||
| **UnifiUPSBMSAnomaly** | BMS anomaly count > 0 for 5m | warning | Battery management system issue; check UPS health |
|
||||
| **UnifiUPSNotCharging** | Not charging and battery < 100% for 30m | warning | Battery not charging; check power or battery |
|
||||
|
||||
*Requires: PDU/UPS devices with vbms_table (e.g. USW-DA-23-POE-UPS)*
|
||||
|
||||
### Controller (unifi-controller)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiControllerUpdateAvailable** | Update available for 1h | info | Controller firmware update available |
|
||||
| **UnifiControllerUnsupportedDevices** | Unsupported device count > 0 for 1h | warning | Devices no longer supported; plan upgrades |
|
||||
|
||||
### Controller Health (unifi-controller-health)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiControllerRecentlyRestarted** | Uptime < 1h for 5m | info | Controller recently restarted; may indicate maintenance or crash |
|
||||
| **UnifiControllerBackupDisabled** | Auto backup disabled for 24h | info | Backups disabled; enable for disaster recovery |
|
||||
|
||||
### Devices (unifi-devices)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiDeviceHighCPU** | CPU > 90% for 10m | warning | Device under heavy load; investigate |
|
||||
| **UnifiDeviceHighMemory** | Memory > 90% for 10m | warning | Device memory pressure; may impact performance |
|
||||
| **UnifiDeviceUpgradeAvailable** | Firmware upgrade available for 1h | info | Device has firmware update available |
|
||||
|
||||
### Site (unifi-site)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiSiteHighDisconnectedDevices** | Disconnected devices > 0 (WLAN/WAN/LAN) for 15m | warning | Devices offline; check power, connectivity, adoption |
|
||||
| **UnifiSitePendingAdoptions** | Pending adoptions > 0 for 1h | info | Devices awaiting adoption |
|
||||
| **UnifiSiteWANDrops** | WAN disconnections in last 1h > 0 | warning | Internet connectivity issues |
|
||||
| **UnifiSiteHighLatency** | Internet latency > 500ms for 10m | warning | Poor internet performance |
|
||||
|
||||
*Requires: save_sites=true*
|
||||
|
||||
### WAN (unifi-wan)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiWANLowUptime** | WAN uptime < 95% for 15m | warning | WAN link unstable; check ISP or cabling |
|
||||
| **UnifiWANPeakDownloadUtilization** | Peak download > 90% of capacity for 10m | info | Download near capacity; consider upgrade |
|
||||
| **UnifiWANPeakUploadUtilization** | Peak upload > 90% of capacity for 10m | info | Upload near capacity; consider upgrade |
|
||||
|
||||
*Requires: WAN metrics (UDM/UDM-Pro/UCG)*
|
||||
|
||||
### DHCP (unifi-dhcp)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiDHCPPoolExhaustion** | Pool utilization > 90% for 15m | warning | DHCP pool nearly full; expand range or reduce lease time |
|
||||
| **UnifiDHCPPoolCritical** | Pool utilization > 98% for 5m | critical | Pool almost exhausted; new devices may not get IPs |
|
||||
|
||||
*Requires: save_dhcp or DHCP lease collection*
|
||||
|
||||
### Rogue AP (unifi-rogue)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiRogueAPDetected** | Any rogue AP detected for 5m | warning | Unauthorized access point; investigate and remediate |
|
||||
|
||||
*Requires: save_rogue=true*
|
||||
|
||||
---
|
||||
|
||||
## Prometheus Recording Rules
|
||||
|
||||
Place `prometheus/unifi-recording-rules.yaml` in your Prometheus `rule_files` to pre-compute aggregates for faster dashboards and simpler alerting.
|
||||
|
||||
### UPS Recording Rules (interval: 1m)
|
||||
|
||||
| Recorded Metric | Expression | Description |
|
||||
|-----------------|------------|-------------|
|
||||
| `unpoller:ups_on_battery:count` | Count of UPSes with battery_mode=1 by site | UPS devices running on battery per site |
|
||||
| `unpoller:ups_min_battery_level_percent:min` | Min battery level by site | Worst battery level per site |
|
||||
| `unpoller:ups_min_runtime_seconds:min` | Min runtime (≥0) by site | Worst runtime remaining per site |
|
||||
| `unpoller:ups_total_power_output_watts:sum` | Sum of power output by site | Total UPS load per site |
|
||||
| `unpoller:ups_total_power_budget_watts:sum` | Sum of power budget by site | Total UPS capacity per site |
|
||||
| `unpoller:ups_bms_anomaly_count:sum` | Sum of devices with BMS anomaly by site | UPSes with BMS issues per site |
|
||||
|
||||
### Device Recording Rules (interval: 1m)
|
||||
|
||||
| Recorded Metric | Expression | Description |
|
||||
|-----------------|------------|-------------|
|
||||
| `unpoller:device_count:by_type` | Count of devices by type (uap, usw, pdu, etc.) per site | Device inventory by type |
|
||||
| `unpoller:device_count:total` | Total device count per site | Total devices per site |
|
||||
| `unpoller:device_high_cpu_count:count` | Count of devices with CPU > 90% per site | Overloaded devices per site |
|
||||
| `unpoller:device_high_memory_count:count` | Count of devices with memory > 90% per site | Memory-pressure devices per site |
|
||||
|
||||
### Controller Recording Rules (interval: 5m)
|
||||
|
||||
| Recorded Metric | Expression | Description |
|
||||
|-----------------|------------|-------------|
|
||||
| `unpoller:controller_update_available:count` | Count of controllers with update available | Controllers needing updates |
|
||||
| `unpoller:controller_unsupported_devices_total:sum` | Sum of unsupported devices | Total unsupported devices across controllers |
|
||||
|
||||
---
|
||||
|
||||
## Loki Alerts
|
||||
|
||||
Place `loki/unifi-alerts.yaml` in your Loki Ruler config. Loki must be run with `-ruler.enable=true` and `-ruler.storage.path` configured.
|
||||
|
||||
### Alarms (unifi-alarms)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiHighAlarmRate** | > 20 alarms in 15m for 5m | warning | Elevated alarm volume; review controller |
|
||||
|
||||
*Requires: save_alarms=true*
|
||||
|
||||
### IDS (unifi-ids)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiIDSEvent** | Any IDS event in 5m for 1m | warning | Intrusion detection triggered; review logs |
|
||||
| **UnifiIDSHighVolume** | > 50 IDS events in 1h for 5m | critical | High IDS volume; possible attack |
|
||||
|
||||
*Requires: save_ids=true*
|
||||
|
||||
### Anomalies (unifi-anomalies)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiAnomalyDetected** | > 5 anomalies in 10m for 5m | warning | Multiple anomalies; check network health |
|
||||
|
||||
*Requires: save_anomalies=true*
|
||||
|
||||
### System Log (unifi-system-log)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiSystemLogCritical** | Any CRITICAL log in 5m for 1m | critical | Critical system log; immediate attention |
|
||||
| **UnifiSystemLogHighSeverity** | > 10 CRITICAL/HIGH/ERROR logs in 15m for 5m | warning | High volume of severe logs |
|
||||
| **UnifiSystemLogAuthFailure** | > 5 auth failure matches in 1h for 5m | warning | Authentication failures; possible brute force |
|
||||
|
||||
*Requires: save_syslog=true (UDM/UDM-Pro) or save_events=true (older controllers)*
|
||||
|
||||
### Events (unifi-events)
|
||||
|
||||
| Alert | Trigger | Severity | Description |
|
||||
|-------|---------|----------|-------------|
|
||||
| **UnifiEventSpike** | > 100 events in 5m for 5m | info | Event spike; may indicate churn or issue |
|
||||
|
||||
*Requires: save_events=true*
|
||||
|
||||
---
|
||||
|
||||
## Configuration
|
||||
|
||||
**Prometheus (prometheus.yml):**
|
||||
|
||||
```yaml
|
||||
rule_files:
|
||||
- /etc/prometheus/rules/unifi-alerts.yaml
|
||||
- /etc/prometheus/rules/unifi-recording-rules.yaml
|
||||
```
|
||||
|
||||
**Loki (loki-config.yaml):**
|
||||
|
||||
```yaml
|
||||
ruler:
|
||||
enable_api: true
|
||||
storage:
|
||||
type: local
|
||||
local:
|
||||
directory: /loki/rules
|
||||
rule_path: /loki/rules-temp
|
||||
alertmanager_url: http://alertmanager:9093
|
||||
```
|
||||
|
||||
Mount the `loki/` directory into your Loki container at `/loki/rules/`.
|
||||
|
||||
## AlertManager Integration
|
||||
|
||||
Both Prometheus and Loki can forward alerts to Alertmanager. Configure Alertmanager receivers (Slack, PagerDuty, email, etc.) as needed.
|
||||
|
||||
## Customization
|
||||
|
||||
- Tune thresholds (battery %, runtime seconds, CPU %, etc.) for your environment
|
||||
- Add or remove labels in `annotations` for your notification channels
|
||||
- Adjust `for` durations to reduce noise or catch issues sooner
|
||||
- Disable alert groups that don't apply (e.g. remove UPS alerts if you have no UPS devices)
|
||||
92
alerts/loki/unifi-alerts.yaml
Normal file
92
alerts/loki/unifi-alerts.yaml
Normal file
@@ -0,0 +1,92 @@
|
||||
# Loki alerting rules for UniFi logs (unPoller Loki output)
|
||||
# Requires: save_alarms, save_ids, save_anomalies, save_events, and/or save_syslog enabled
|
||||
groups:
|
||||
- name: unifi-alarms
|
||||
rules:
|
||||
- alert: UnifiHighAlarmRate
|
||||
expr: |
|
||||
sum by (site_name, source) (count_over_time({application="unifi_alarm"}[15m])) > 20
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "High UniFi alarm rate"
|
||||
description: "{{ $value }} alarms in 15m for site {{ $labels.site_name }}"
|
||||
|
||||
- name: unifi-ids
|
||||
rules:
|
||||
- alert: UnifiIDSEvent
|
||||
expr: |
|
||||
count_over_time({application="unifi_ids"}[5m]) > 0
|
||||
for: 1m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UniFi IDS event detected"
|
||||
description: "Intrusion detection event(s) from UniFi - review logs"
|
||||
|
||||
- alert: UnifiIDSHighVolume
|
||||
expr: |
|
||||
sum by (site_name) (count_over_time({application="unifi_ids"}[1h])) > 50
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "High UniFi IDS event volume"
|
||||
description: "{{ $value }} IDS events in 1h for site {{ $labels.site_name }} - possible attack"
|
||||
|
||||
- name: unifi-anomalies
|
||||
rules:
|
||||
- alert: UnifiAnomalyDetected
|
||||
expr: |
|
||||
count_over_time({application="unifi_anomaly"}[10m]) > 5
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UniFi anomalies detected"
|
||||
description: "Multiple anomalies in 10m - review network health"
|
||||
|
||||
- name: unifi-system-log
|
||||
rules:
|
||||
- alert: UnifiSystemLogCritical
|
||||
expr: |
|
||||
sum by (site_name, source) (count_over_time({application="unifi_system_log", severity="CRITICAL"}[5m])) > 0
|
||||
for: 1m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "UniFi CRITICAL system log on {{ $labels.site_name }}"
|
||||
description: "{{ $value }} CRITICAL log(s) in 5m - immediate attention required"
|
||||
|
||||
- alert: UnifiSystemLogHighSeverity
|
||||
expr: |
|
||||
sum by (site_name, severity) (count_over_time({application="unifi_system_log", severity=~"CRITICAL|HIGH|ERROR"}[15m])) > 10
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "High-severity UniFi system log volume"
|
||||
description: "{{ $value }} {{ $labels.severity }} logs in 15m for site {{ $labels.site_name }}"
|
||||
|
||||
- alert: UnifiSystemLogAuthFailure
|
||||
expr: |
|
||||
sum by (site_name) (count_over_time({application="unifi_system_log"} |~ "(?i)(login failed|auth failed|authentication failure)"[1h])) > 5
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UniFi authentication failures on {{ $labels.site_name }}"
|
||||
description: "{{ $value }} auth failure(s) in 1h - possible brute force or credential leak"
|
||||
|
||||
- name: unifi-events
|
||||
rules:
|
||||
- alert: UnifiEventSpike
|
||||
expr: |
|
||||
sum by (site_name) (count_over_time({application="unifi_event"}[5m])) > 100
|
||||
for: 5m
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "UniFi event spike"
|
||||
description: "{{ $value }} events in 5m - may indicate network churn or issue"
|
||||
234
alerts/prometheus/unifi-alerts.yaml
Normal file
234
alerts/prometheus/unifi-alerts.yaml
Normal file
@@ -0,0 +1,234 @@
|
||||
# Prometheus alerting rules for UniFi infrastructure (unPoller metrics)
|
||||
# Default namespace: unpoller. Adjust metric names if using a custom namespace.
|
||||
groups:
|
||||
- name: unifi-ups
|
||||
rules:
|
||||
- alert: UnifiUPSLowBattery
|
||||
expr: unpoller_device_ups_battery_level_percent < 20
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Low UPS battery on {{ $labels.device_name }}"
|
||||
description: "UPS {{ $labels.device_name }} at {{ $value }}% battery (site: {{ $labels.site_name }})"
|
||||
|
||||
- alert: UnifiUPSCriticalBattery
|
||||
expr: unpoller_device_ups_battery_level_percent < 10
|
||||
for: 2m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "Critical UPS battery on {{ $labels.device_name }}"
|
||||
description: "UPS {{ $labels.device_name }} at {{ $value }}% battery - prepare for shutdown"
|
||||
|
||||
- alert: UnifiUPSOnBattery
|
||||
expr: unpoller_device_ups_battery_mode == 1
|
||||
for: 1m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UPS {{ $labels.device_name }} running on battery"
|
||||
description: "Power outage or AC loss - UPS {{ $labels.device_name }} on battery (site: {{ $labels.site_name }})"
|
||||
|
||||
- alert: UnifiUPSLowRuntime
|
||||
expr: unpoller_device_ups_battery_time_remaining_seconds < 300 and unpoller_device_ups_battery_time_remaining_seconds >= 0
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Low UPS runtime on {{ $labels.device_name }}"
|
||||
description: "UPS {{ $labels.device_name }} has {{ $value | humanizeDuration }} runtime remaining"
|
||||
|
||||
- alert: UnifiUPSHighLoad
|
||||
expr: unpoller_device_ups_load_percent > 80
|
||||
for: 10m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "High UPS load on {{ $labels.device_name }}"
|
||||
description: "UPS {{ $labels.device_name }} load at {{ $value }}% of capacity"
|
||||
|
||||
- alert: UnifiUPSBMSAnomaly
|
||||
expr: unpoller_device_ups_bms_anomaly_count > 0
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UPS BMS anomaly on {{ $labels.device_name }}"
|
||||
description: "Battery management anomaly detected on {{ $labels.device_name }}"
|
||||
|
||||
- alert: UnifiUPSNotCharging
|
||||
expr: unpoller_device_ups_battery_charging == 0 and unpoller_device_ups_battery_level_percent < 100
|
||||
for: 30m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "UPS {{ $labels.device_name }} not charging"
|
||||
description: "Battery at {{ $value }}% but not charging - check power or battery health"
|
||||
|
||||
- name: unifi-controller
|
||||
rules:
|
||||
- alert: UnifiControllerUpdateAvailable
|
||||
expr: unpoller_controller_update_available == 1
|
||||
for: 1h
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "UniFi controller update available ({{ $labels.hostname }})"
|
||||
description: "Controller {{ $labels.hostname }} has an update available"
|
||||
|
||||
- alert: UnifiControllerUnsupportedDevices
|
||||
expr: unpoller_controller_unsupported_device_count > 0
|
||||
for: 1h
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Unsupported devices on controller {{ $labels.hostname }}"
|
||||
description: "{{ $value }} unsupported device(s) on controller"
|
||||
|
||||
- name: unifi-devices
|
||||
rules:
|
||||
- alert: UnifiDeviceHighCPU
|
||||
expr: unpoller_device_cpu_utilization_ratio > 0.9
|
||||
for: 10m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "High CPU on {{ $labels.name }}"
|
||||
description: "Device {{ $labels.name }} ({{ $labels.type }}) CPU at {{ $value | humanize }}"
|
||||
|
||||
- alert: UnifiDeviceHighMemory
|
||||
expr: unpoller_device_memory_utilization_ratio > 0.9
|
||||
for: 10m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "High memory on {{ $labels.name }}"
|
||||
description: "Device {{ $labels.name }} memory at {{ $value | humanize }}"
|
||||
|
||||
- alert: UnifiDeviceUpgradeAvailable
|
||||
expr: unpoller_device_upgradable == 1
|
||||
for: 1h
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "Device {{ $labels.name }} has upgrade available"
|
||||
description: "{{ $labels.type }} device {{ $labels.name }} has firmware update available (site: {{ $labels.site_name }})"
|
||||
|
||||
- name: unifi-site
|
||||
rules:
|
||||
- alert: UnifiSiteHighDisconnectedDevices
|
||||
expr: unpoller_site_disconnected{subsystem=~"wlan|wan|lan"} > 0
|
||||
for: 15m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Disconnected devices on {{ $labels.site_name }} ({{ $labels.subsystem }})"
|
||||
description: "{{ $value }} device(s) disconnected in {{ $labels.subsystem }} subsystem"
|
||||
|
||||
- alert: UnifiSitePendingAdoptions
|
||||
expr: unpoller_site_pending > 0
|
||||
for: 1h
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "Pending device adoptions on {{ $labels.site_name }}"
|
||||
description: "{{ $value }} device(s) pending adoption (subsystem: {{ $labels.subsystem }})"
|
||||
|
||||
- alert: UnifiSiteWANDrops
|
||||
expr: increase(unpoller_site_intenet_drops_total[1h]) > 0
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "WAN disconnections on {{ $labels.site_name }}"
|
||||
description: "WAN dropped {{ $value }} time(s) in the last hour"
|
||||
|
||||
- alert: UnifiSiteHighLatency
|
||||
expr: unpoller_site_latency_seconds{subsystem="www"} > 0.5
|
||||
for: 10m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "High internet latency on {{ $labels.site_name }}"
|
||||
description: "Latency {{ $value }}s exceeds 500ms threshold"
|
||||
|
||||
- name: unifi-wan
|
||||
rules:
|
||||
- alert: UnifiWANLowUptime
|
||||
expr: unpoller_wan_uptime_percentage < 95
|
||||
for: 15m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Low WAN uptime on {{ $labels.wan_name }}"
|
||||
description: "WAN {{ $labels.wan_name }} uptime at {{ $value }}% (site: {{ $labels.site_name }})"
|
||||
|
||||
- alert: UnifiWANPeakDownloadUtilization
|
||||
expr: unpoller_wan_peak_download_percent > 90
|
||||
for: 10m
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "WAN download near capacity on {{ $labels.wan_name }}"
|
||||
description: "Peak download at {{ $value }}% - consider upgrading or load balancing"
|
||||
|
||||
- alert: UnifiWANPeakUploadUtilization
|
||||
expr: unpoller_wan_peak_upload_percent > 90
|
||||
for: 10m
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "WAN upload near capacity on {{ $labels.wan_name }}"
|
||||
description: "Peak upload at {{ $value }}% - consider upgrading or load balancing"
|
||||
|
||||
- name: unifi-dhcp
|
||||
rules:
|
||||
- alert: UnifiDHCPPoolExhaustion
|
||||
expr: unpoller_dhcp_utilization_percent > 90
|
||||
for: 15m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "DHCP pool nearly exhausted on {{ $labels.network }}"
|
||||
description: "DHCP utilization at {{ $value }}% - expand pool or reduce lease time"
|
||||
|
||||
- alert: UnifiDHCPPoolCritical
|
||||
expr: unpoller_dhcp_utilization_percent > 98
|
||||
for: 5m
|
||||
labels:
|
||||
severity: critical
|
||||
annotations:
|
||||
summary: "DHCP pool critically low on {{ $labels.network }}"
|
||||
description: "Utilization at {{ $value }}% - new devices may not get IP addresses"
|
||||
|
||||
- name: unifi-rogue
|
||||
rules:
|
||||
- alert: UnifiRogueAPDetected
|
||||
expr: count(unpoller_rogueap_rssi) > 0
|
||||
for: 5m
|
||||
labels:
|
||||
severity: warning
|
||||
annotations:
|
||||
summary: "Rogue AP detected on {{ $labels.site_name }}"
|
||||
description: "Unauthorized access point(s) detected - review and take action"
|
||||
|
||||
- name: unifi-controller-health
|
||||
rules:
|
||||
- alert: UnifiControllerRecentlyRestarted
|
||||
expr: unpoller_controller_uptime_seconds < 3600
|
||||
for: 5m
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "Controller {{ $labels.hostname }} recently restarted"
|
||||
description: "Uptime {{ $value | humanizeDuration }} - may indicate maintenance or crash"
|
||||
|
||||
- alert: UnifiControllerBackupDisabled
|
||||
expr: unpoller_controller_autobackup_enabled == 0
|
||||
for: 24h
|
||||
labels:
|
||||
severity: info
|
||||
annotations:
|
||||
summary: "Auto backup disabled on {{ $labels.hostname }}"
|
||||
description: "Controller has automatic backups disabled - enable for disaster recovery"
|
||||
60
alerts/prometheus/unifi-recording-rules.yaml
Normal file
60
alerts/prometheus/unifi-recording-rules.yaml
Normal file
@@ -0,0 +1,60 @@
|
||||
# Prometheus recording rules for UniFi infrastructure (unPoller metrics)
|
||||
# Pre-compute aggregates for dashboards and simpler alerting.
|
||||
# Default namespace: unpoller. Adjust metric names if using a custom namespace.
|
||||
groups:
|
||||
- name: unifi-ups-recording
|
||||
interval: 1m
|
||||
rules:
|
||||
# Count of UPS devices running on battery per site (for "any UPS on battery" alerts/dashboards)
|
||||
- record: unpoller:ups_on_battery:count
|
||||
expr: count by (site_name, source) (unpoller_device_ups_battery_mode == 1)
|
||||
|
||||
# Minimum battery level across UPSes per site (worst-case for multi-UPS sites)
|
||||
- record: unpoller:ups_min_battery_level_percent:min
|
||||
expr: min by (site_name, source) (unpoller_device_ups_battery_level_percent)
|
||||
|
||||
# Minimum runtime remaining across UPSes per site (worst-case; excludes -1 unknown)
|
||||
- record: unpoller:ups_min_runtime_seconds:min
|
||||
expr: min by (site_name, source) (unpoller_device_ups_battery_time_remaining_seconds >= 0)
|
||||
|
||||
# Total power output across UPSes per site (capacity planning)
|
||||
- record: unpoller:ups_total_power_output_watts:sum
|
||||
expr: sum by (site_name, source) (unpoller_device_ups_power_output_watts)
|
||||
|
||||
# Total power budget across UPSes per site
|
||||
- record: unpoller:ups_total_power_budget_watts:sum
|
||||
expr: sum by (site_name, source) (unpoller_device_ups_power_budget_watts)
|
||||
|
||||
# Count of UPS devices with BMS anomalies per site
|
||||
- record: unpoller:ups_bms_anomaly_count:sum
|
||||
expr: sum by (site_name, source) (unpoller_device_ups_bms_anomaly_count > 0)
|
||||
|
||||
- name: unifi-devices-recording
|
||||
interval: 1m
|
||||
rules:
|
||||
# Device count by type per site (capacity dashboards)
|
||||
- record: unpoller:device_count:by_type
|
||||
expr: count by (site_name, source, type) (unpoller_device_info)
|
||||
|
||||
# Total device count per site
|
||||
- record: unpoller:device_count:total
|
||||
expr: count by (site_name, source) (unpoller_device_info)
|
||||
|
||||
# Count of devices with high CPU per site
|
||||
- record: unpoller:device_high_cpu_count:count
|
||||
expr: count by (site_name, source) (unpoller_device_cpu_utilization_ratio > 0.9)
|
||||
|
||||
# Count of devices with high memory per site
|
||||
- record: unpoller:device_high_memory_count:count
|
||||
expr: count by (site_name, source) (unpoller_device_memory_utilization_ratio > 0.9)
|
||||
|
||||
- name: unifi-controller-recording
|
||||
interval: 5m
|
||||
rules:
|
||||
# Count of controllers with updates available (multi-controller orgs)
|
||||
- record: unpoller:controller_update_available:count
|
||||
expr: count(unpoller_controller_update_available == 1)
|
||||
|
||||
# Total unsupported devices across all controllers
|
||||
- record: unpoller:controller_unsupported_devices_total:sum
|
||||
expr: sum(unpoller_controller_unsupported_device_count)
|
||||
2
go.mod
2
go.mod
@@ -12,7 +12,7 @@ require (
|
||||
github.com/prometheus/common v0.67.5
|
||||
github.com/spf13/pflag v1.0.10
|
||||
github.com/stretchr/testify v1.11.1
|
||||
github.com/unpoller/unifi/v5 v5.15.0
|
||||
github.com/unpoller/unifi/v5 v5.16.0
|
||||
golang.org/x/crypto v0.47.0
|
||||
golang.org/x/term v0.39.0
|
||||
golift.io/cnfg v0.2.3
|
||||
|
||||
4
go.sum
4
go.sum
@@ -77,8 +77,8 @@ github.com/stretchr/testify v1.8.0/go.mod h1:yNjHg4UonilssWZ8iaSj1OCr/vHnekPRkoO
|
||||
github.com/stretchr/testify v1.8.1/go.mod h1:w2LPCIKwWwSfY2zedu0+kehJoqGctiVI29o6fzry7u4=
|
||||
github.com/stretchr/testify v1.11.1 h1:7s2iGBzp5EwR7/aIZr8ao5+dra3wiQyKjjFuvgVKu7U=
|
||||
github.com/stretchr/testify v1.11.1/go.mod h1:wZwfW3scLgRK+23gO65QZefKpKQRnfz6sD981Nm4B6U=
|
||||
github.com/unpoller/unifi/v5 v5.15.0 h1:9xYBmboWBcY4Cv8ARbWMjBlAUNVlG7TIuX+aRf6mcUE=
|
||||
github.com/unpoller/unifi/v5 v5.15.0/go.mod h1:vSIXIclPG9dpKxUp+pavfgENHWaTZXvDg7F036R1YCo=
|
||||
github.com/unpoller/unifi/v5 v5.16.0 h1:FowfkJ7wbMoySFcqOJG2IJH9pOGTUnPpKNNG9vHl2/I=
|
||||
github.com/unpoller/unifi/v5 v5.16.0/go.mod h1:vSIXIclPG9dpKxUp+pavfgENHWaTZXvDg7F036R1YCo=
|
||||
github.com/yuin/goldmark v1.3.5/go.mod h1:mwnBkeHKe2W/ZEtQ+71ViKU8L12m81fl3OWwC1Zlc8k=
|
||||
go.uber.org/goleak v1.3.0 h1:2K3zAYmnTNqV73imy9J1T3WC+gmCePx2hEGkimedGto=
|
||||
go.uber.org/goleak v1.3.0/go.mod h1:CoHD4mav9JJNrW/WLlf7HGZPjdw8EucARQHekz1X6bE=
|
||||
|
||||
@@ -55,7 +55,7 @@ func (u *InfluxUnifi) batchUDMtemps(temps []unifi.Temperature) map[string]any {
|
||||
output := make(map[string]any)
|
||||
|
||||
for _, t := range temps {
|
||||
output["temp_"+sanitizeName(t.Name)] = t.Value
|
||||
output["temp_"+sanitizeName(t.Name)] = int64(t.Value)
|
||||
}
|
||||
|
||||
return output
|
||||
|
||||
@@ -58,6 +58,21 @@ type pdu struct {
|
||||
OutletPower *prometheus.Desc
|
||||
OutletPowerFactor *prometheus.Desc
|
||||
OutletVoltage *prometheus.Desc
|
||||
// UPS battery health (vbms_table)
|
||||
BatteryLevelPercent *prometheus.Desc
|
||||
BatteryTimeRemaining *prometheus.Desc
|
||||
BatteryCharging *prometheus.Desc
|
||||
BatteryMode *prometheus.Desc
|
||||
BatteriesAvailable *prometheus.Desc
|
||||
BatteriesReady *prometheus.Desc
|
||||
PowerBudgetWatts *prometheus.Desc
|
||||
PowerOutputWatts *prometheus.Desc
|
||||
PowerFactor *prometheus.Desc
|
||||
OutputVoltage *prometheus.Desc
|
||||
OutputCurrentAmps *prometheus.Desc
|
||||
LoadPercent *prometheus.Desc
|
||||
BMSAnomalyCount *prometheus.Desc
|
||||
PowerCycleOnRecoveryEnabled *prometheus.Desc
|
||||
}
|
||||
|
||||
func descPDU(ns string) *pdu {
|
||||
@@ -73,6 +88,7 @@ func descPDU(ns string) *pdu {
|
||||
labelO := []string{
|
||||
"outlet_description", "outlet_index", "outlet_name", "site_name", "name", "source", "tag",
|
||||
}
|
||||
labelUPS := []string{"site_name", "device_name", "device_mac", "source", "tag"}
|
||||
nd := prometheus.NewDesc
|
||||
|
||||
return &pdu{
|
||||
@@ -128,6 +144,21 @@ func descPDU(ns string) *pdu {
|
||||
OutletPower: nd(outlet+"outlet_power", "Outlet Power", labelO, nil),
|
||||
OutletPowerFactor: nd(outlet+"outlet_power_factor", "Outlet Power Factor", labelO, nil),
|
||||
OutletVoltage: nd(outlet+"outlet_voltage", "Outlet Voltage", labelO, nil),
|
||||
// UPS battery health (vbms_table)
|
||||
BatteryLevelPercent: nd(ns+"ups_battery_level_percent", "Battery charge level (0-100%)", labelUPS, nil),
|
||||
BatteryTimeRemaining: nd(ns+"ups_battery_time_remaining_seconds", "Estimated runtime on battery", labelUPS, nil),
|
||||
BatteryCharging: nd(ns+"ups_battery_charging", "Battery charging (1/0)", labelUPS, nil),
|
||||
BatteryMode: nd(ns+"ups_battery_mode", "Running on battery (1/0)", labelUPS, nil),
|
||||
BatteriesAvailable: nd(ns+"ups_batteries_available", "Number of batteries available", labelUPS, nil),
|
||||
BatteriesReady: nd(ns+"ups_batteries_ready", "Number of batteries ready", labelUPS, nil),
|
||||
PowerBudgetWatts: nd(ns+"ups_power_budget_watts", "Total power budget capacity", labelUPS, nil),
|
||||
PowerOutputWatts: nd(ns+"ups_power_output_watts", "Current power output", labelUPS, nil),
|
||||
PowerFactor: nd(ns+"ups_power_factor", "Power factor (0-1)", labelUPS, nil),
|
||||
OutputVoltage: nd(ns+"ups_output_voltage", "Output voltage", labelUPS, nil),
|
||||
OutputCurrentAmps: nd(ns+"ups_output_current_amps", "Output current in amps", labelUPS, nil),
|
||||
LoadPercent: nd(ns+"ups_load_percent", "Load as percentage of capacity", labelUPS, nil),
|
||||
BMSAnomalyCount: nd(ns+"ups_bms_anomaly_count", "Battery management anomalies", labelUPS, nil),
|
||||
PowerCycleOnRecoveryEnabled: nd(ns+"ups_power_cycle_on_recovery_enabled", "Auto power cycle on AC recovery enabled (1/0)", labelUPS, nil),
|
||||
}
|
||||
}
|
||||
|
||||
@@ -147,6 +178,10 @@ func (u *promUnifi) exportPDU(r report, d *unifi.PDU) {
|
||||
u.exportPDUstats(r, labels, d.Stat.Sw)
|
||||
u.exportPDUPrtTable(r, labels, d.PortTable)
|
||||
u.exportPDUOutletTable(r, labels, d.OutletTable, d.OutletOverrides)
|
||||
|
||||
if d.VBMSTable != nil {
|
||||
u.exportPDUVBMS(r, d, append([]string{d.SiteName, d.Name, d.Mac, d.SourceName}, tag))
|
||||
}
|
||||
u.exportBYTstats(r, labels, d.TxBytes, d.RxBytes)
|
||||
u.exportSYSstats(r, labels, d.SysStats, d.SystemStats)
|
||||
u.exportSTAcount(r, labels, d.UserNumSta, d.GuestNumSta)
|
||||
@@ -199,6 +234,42 @@ func (u *promUnifi) exportPDUstats(r report, labels []string, sw *unifi.Sw) {
|
||||
})
|
||||
}
|
||||
|
||||
// exportPDUVBMS exports UPS battery health metrics from vbms_table (UPS devices only).
|
||||
func (u *promUnifi) exportPDUVBMS(r report, d *unifi.PDU, labels []string) {
|
||||
vbms := d.VBMSTable
|
||||
|
||||
r.send([]*metric{
|
||||
{u.PDU.BMSAnomalyCount, gauge, vbms.BMSRunAnomaly, labels},
|
||||
{u.PDU.BatteryMode, gauge, vbms.IsBatteryMode.Val, labels},
|
||||
{u.PDU.PowerCycleOnRecoveryEnabled, gauge, d.OutletPowerCycleOnACRecoveryEnabled.Val, labels},
|
||||
})
|
||||
|
||||
if vbms.BattPool == nil {
|
||||
return
|
||||
}
|
||||
|
||||
bp := vbms.BattPool
|
||||
loadPct := 0.0
|
||||
|
||||
if bp.DeviceTotalPowerBudget.Val > 0 {
|
||||
loadPct = (bp.DeviceTotalPowerOutput.Val / bp.DeviceTotalPowerBudget.Val) * 100
|
||||
}
|
||||
|
||||
r.send([]*metric{
|
||||
{u.PDU.BatteryLevelPercent, gauge, bp.BatteryLevel, labels},
|
||||
{u.PDU.BatteryTimeRemaining, gauge, bp.TimeToRemain, labels},
|
||||
{u.PDU.BatteryCharging, gauge, bp.IsCharging.Val, labels},
|
||||
{u.PDU.BatteriesAvailable, gauge, bp.BattAvailableCnt, labels},
|
||||
{u.PDU.BatteriesReady, gauge, bp.ReadyCnt, labels},
|
||||
{u.PDU.PowerBudgetWatts, gauge, bp.DeviceTotalPowerBudget, labels},
|
||||
{u.PDU.PowerOutputWatts, gauge, bp.DeviceTotalPowerOutput, labels},
|
||||
{u.PDU.PowerFactor, gauge, bp.DeviceTotalPowerFactor, labels},
|
||||
{u.PDU.OutputVoltage, gauge, bp.DeviceOutputVoltage, labels},
|
||||
{u.PDU.OutputCurrentAmps, gauge, bp.DeviceOutputCurrent, labels},
|
||||
{u.PDU.LoadPercent, gauge, loadPct, labels},
|
||||
})
|
||||
}
|
||||
|
||||
// Switch Port Table.
|
||||
func (u *promUnifi) exportPDUPrtTable(r report, labels []string, pt []unifi.Port) {
|
||||
// Per-port data on a switch
|
||||
|
||||
Reference in New Issue